Evaluating
Your Home's Wiring System
Is knob and tube wiring adequate for modern living? Is your home's
electrical service panel adequate? Here's a guide to inspecting older wiring.
Editor's note: This story is
adapted from the U.S. Department of Housing and Urban Development's Residential Rehabilitation Inspection
Guide, 2000.

Found fairly often in houses built before 1930, "knob and
tube" wiring should be carefully inspected to failed insulation and other safety issues. If has adequate
capacity and is otherwise safe, it is still legal in many places.
Electrical systems for small residential
buildings are usually simple in concept and layout. Primary components are the:
- service entry,
- panel board, and
- branch circuits.
In unaltered buildings built since about
1940, the electrical system is likely to be intact and safe, although it may not provide the capacity required
for the planned reuse of the building. Electrical capacity can be easily increased by bringing additional
capacity in from the street and adding a larger panel board between the service entry and the existing panel.
Existing circuits can continue to use the existing panel and new circuits can be fed through the new
panel.
The electrical systems of small
residential buildings built prior to about1940 may require overhaul or replacement, depending on rehabilitation
plans and the condition of the electrical system. Parts of these older systems may function very adequately and
they can often be retained if the rehabilitation isn't extensive and the load-carrying capacity is
adequate.
A thorough and informed assessment of the
electrical system will determine the extent to which it can be reused. This assessment should be conducted only
by a qualified electrician who is experienced in residential electrical work. When universal design is a part
of a rehabilitation, consult the Housing and Urban Development publication Residential Remodeling and Universal Design for detailed information about electrical devices.
| Assessing the electrical capacity (ampacity) of the
building's existing electrical service |
To determine the capacity (measured in
amperes) of the building's existing electrical service at the main panel-board, check the
following:
- The ampacity of the service entry conductor,
which may be determined by noting the markings (if any) on the conductor cable and finding its rated
ampacity in the National Electrical Code, Table
310-16, or applicable local code. If the service entry
conductor is in conduit, look for markings on the conductor wires as they emerge from the conduit into
the panel board. If all conductors are unmarked, have an electrician evaluate
them.
- The ampere rating on the panel board or service
disconnect switch, as listed on the manufacturer's data plate.
- The ampere rating marked on the main circuit
breaker or main building fuse(s). This rating should never be higher than the above two ratings; if it
is, the system should not be used until it is evaluated by an electrician.
The building's service capacity
is the lowest of the above three figures.
Once the service ampacity has been
determined, compare it to the estimated ampacity the building will require after rehabilitation. If the
estimated ampacity exceeds the existing ampacity, the building's electrical service will need upgrading. The
method for estimating required ampacity is found in the National
Electrical Code, Article 220.
Similarly, the service capacity of each
branch circuit can be determined by checking the markings on each branch circuit conductor. If no markings can
be found, a plastic wire gauge may be used to measure the wire size (with the power disconnected), although an
experienced person can often determine the size by eye. Find the ampere rating of the conductor, either by its
markings or wire size, in the National Electrical Code, Table
310-16, or applicable local code.
The safety standards for the following
assessment procedures are generally based on the requirements of the National Electrical
Code.

Typical service equipment
Inspect for the following conditions in the
electrical service between the street and the main panel board:
- Overhead wires. Check that overhead wires from
the street are no lower than 10 feet above the ground, not in contact with tree branches or other
obstacles, and not reachable from nearby windows or other accessible areas. Make sure that the wires
are securely attached to the building with insulated anchors, and have drip loops where they enter the
weather head. Spliced connections at the service entrance should be well wrapped, and bare wires from
the street should be replaced by the utility company. Wires should not be located over swimming
pools.
- Electric meter. Check that the electric meter and
its base are weatherproof, and that the meter is functional, has not been tampered with, and is
securely fastened. Advise the utility company of any problems with the
meter.
- Seismic vulnerability. If the building is in a
seismic zone, check the electrical service for vulnerability to differential movement between the
exterior and interior. Look for flexible connections.
- Service entrance conductor. Ensure that the
service entrance conductor has no splices and that its insulation is completely intact. If the main
panel board is located inside the building, the conductor's passage through the wall should be sealed
against moisture. Where aluminum conductors are used, their terminations at all service equipment
should be cleaned with an oxide inhibitor and tightened by an electrician or replaced with equal
capacity copper conductors. When it is necessary to replace an overhead service entry, have it replaced
with an underground service entry.
- Type of power available. Not every jurisdiction
provides the same kind of electrical power. Philadelphia, for example, has two-phase electrical power
in some locations rather than the more common single-phase. Check with the power company to determine
the characteristics of the power available.
The main panel board is the distribution center for
electric service within the building and protects the house wiring from overloads. Inspect the panel board as
follows:
- Condition and location. Check the overall
condition of the panel board. Water marks or rust on a panel mounted inside the building may indicate
water infiltration along the path of the service entrance conductor. Panel boards mounted outdoors
should be watertight and tamper proof. Panels mounted indoors should be located as closely as possible
to where the service entrance conductor enters the building and should be easily accessible. The panel
board should have a workable and secure cover.
- Amperage rating. The amperage rating of the main
disconnect should not be higher than the amperage capacity of the service entrance conductor or the
panel board. If the rating is higher (indicating unapproved work has been done), more branch circuits
may be connected to it than the service entrance conductor is capable of supplying. This is a serious
hazard and should be corrected.
- Voltage rating. The voltage rating of the panel
board (as marked on the manufacturer's data plate) should match the voltage of the incoming electrical
service.
- Test: The actual voltage rating of the incoming
electrical service can be checked with a voltmeter. This test should be performed by an electrician.
Usually three service conductors indicates 120/240 volt current, and two conductors indicates 120 volt
current.
- Grounding. (See illustration below) Verify that
the panel board is properly grounded. Its grounding conductor should run to an exterior grounding
electrode or be clamped to the metal water service inlet pipe between the exterior wall and the water
meter. If it is attached on the house side of the meter, the meter should be jumpered to ensure proper
electrical continuity to the earth. Make sure that the ground conductor is securely and properly
clamped to the pipe-often it is not, and occasionally it is disconnected altogether. Ensure also that
the grounding conductor is not attached to a natural gas pipe, to an inactive pipe that may be cut off
on the exterior side of the wall, or to a pipe that is connected to a plastic water service entry line.
If the grounding conductor is attached to an exterior grounding electrode driven into the earth, verify
that the electrode is installed in accordance with local code. Many older buildings will have the
ground connected to the cold water pipe. If this is the case and the building needs to conform to the
current code, an alternate ground is required. Typical electrical service entry and main panel board
for a single family residence. This type of grounding applies only if the water pipe is metal. If the
water pipe is plastic, a separate driven ground rod is required.

Typical electrical
service entry and main panel board for a single family residence. This type of grounding applies only if the
water pipe is metal. If the water pipe is plastic, a separate driven ground rod is required.
- Test. An electrical ground (resistance-to-ground)
test may be used to determine whether the electrical system is well grounded to the earth. The test
requires the use of an ohm-meter and should be performed by an electrician.
- Over-current protection. Check the rating of the fuse
or circuit breaker for each branch circuit. The amperage of the fuse or circuit breaker should not exceed
the capacity of the wiring in the branch circuit it protects. Most household circuits use #14 copper wire,
which should have 15 amp protection. There may be one or more circuits with #12 copper wire, which should
have 20 amp protection. Large appliances, such as electric water heaters and central air conditioners, may
require 30 amp service, which is normally supplied by #10 copper wire. If there is an electric range, it
would require a 40 or 50 amp service with #6 copper wire. Central air conditioning equipment will have an
over-current protection requirement on the nameplate. Aluminum wire must be one size larger than copper
wire in each case (e.g., #14 to #12), but it should not be used for 15 and 20 amp circuits. Make sure that
no circuit has a fuse or circuit breaker with a higher ampere rating than its wiring is designed to carry.
Air conditioners and other equipment with motors may have circuit breakers up to 175 percent ampacity of
the conductor rating to allow for starting current. Look near the panel board for an inordinate number of
new or blown fuses, or breakers taped in the "on" position. Be suspicious of 20 or 25 amp fuses on
household lighting circuits. These are signs of frequent overloads and inadequate electrical service. Other
indications of overloading are the odor of burned insulation, evidence of melted insulation, discolored
copper contact points in the fuse holders, and warm fuses or circuit
breakers.
- Test: Flip all circuit breakers on and off manually
to make sure they are in good operating condition. A commercially available circuit breaker and resistance
tester, which can simulate an overload condition, can be used to test each breaker. Such a test should be
performed by an electrician. Note that this test is not recommended for computers, VCR's, clocks, and many
similar devices.
- Many older residential buildings have more than one
panel-board or fused devices. Check that all supplementary over-current devices are located in metal boxes
and that they are not in the vicinity of easily ignitable materials. All panel boards must have covers. It
should be possible to turn off all electrical power to a dwelling from a single
location.
The oldest types of residential wiring systems are seldom
encountered today. They include open wires on metal cleats, wiring laid directly in plaster, and wiring in
wooden molding. These systems proved quite hazardous.
The oldest wiring system that may still be acceptable, and
one still found fairly often in houses built before 1930, is "knob and tube." This system utilizes porcelain
insulators (knobs) for running wires through unobstructed spaces, and porcelain tubes for running wires through
building components such as studs and joists.
Note whether knob and tube wiring splices are mechanically
twisted, soldered, and taped, as required. Knob and tube wiring should be replaced during rehabilitation; but
if it is properly installed, needs no modification, has adequate capacity, is properly grounded, has no failed
insulation, and is otherwise in good condition, it can be an acceptable wiring system and is still legal in
some localities.

Check with local building code officials. Also check the
terms and conditions of the home insurance policy in force to see if knob and tube wiring is excluded. In San
Diego, knob and tube wiring does not meet code requirements. It is very difficult to purchase homeowners
insurance for properties containing knob and tube wiring. The greatest problem with such wiring is its
insulation, which turns dry and brittle with age and often falls off on contact, leaving the wire exposed.
Insulation that can be seen to have failed also will likely have failed where wiring is concealed. If any
failed insulation is observed, the knob and tube wiring should be replaced.
Other approved wire types include:
- NM (non-metallic) cable, often called by the trade
name "Romex," a plastic covered-cable for use in dry locations (older NM cable may be cloth
covered).
- NMC, similar to NM but rated for damp
locations.
- UF (underground feeder), a plastic-covered waterproof
cable for use underground.
- AC (armored cable), also called BX, a flexible
metal-covered cable.
- MC (metal-clad cable), a flexible metal-covered cable
with a green insulated ground conductor.
- EMT (electrical metallic tubing), also called "thin
wall," a metal conduit through which the wires are run in areas where maximum protection is
required.
In
the picture at right, the armored cable and junction box are in good shape and can be reused, even if the
lighting fixture is relocated.
Check branch circuits for the following:
- Marking. The function of each branch circuit should
be clearly and legibly marked at its disconnect, fuse, circuit breaker, or on the directory on the panel
board.
- Connected loads. Trace branch circuit conductors to
determine that their connected load does not exceed their rating (e.g., a 30 amp clothes dryer connected to
a 20 amp circuit). Generally speaking, each dwelling unit should have two to four 15 amp circuits for
lighting and convenience outlets; two 20 amp circuits for appliances in the kitchen, dining, and laundry
areas; and separate circuits of appropriate ampacity for large appliances such as dryers, ranges,
disposals, dishwashers, and water heaters.
- Check the size and length of all branch circuit
wiring against the requirements of the local electrical code. Buildings built before 1980 may be considered
to have an inadequate number of circuits because present day codes require a separate laundry circuit and a
separate circuit for the bathroom receptacle. For air conditioning units, many local codes will allow one
wire size smaller than called for in the disconnect.
- Test: A voltmeter may be used to measure voltage drop
due to excessive branch circuit length, poor wiring connections, or undersized wire. Measurements must be
made under a connected load. This test should be performed by an
electrician.
- Grounding. It is best that all circuits be grounded
to the panel board, but this was not required by the National Electrical Code prior to 1965. Do not assume
that circuits in metal cable are grounded without testing each outlet. Also, do not assume that three-prong
plug convenience outlets are connected to ground. Remove each one to observe the presence of a connected
ground wire. Check to see whether GFI (ground fault interruption) type receptacles have been installed in
laundries, kitchens, and bathrooms, and test their operation. These types of receptacles were not required
before 1990, but are easily installed as replacements.
- Test: Commercially available circuit analyzers can be
used for checking the following circuit conditions: open ground, open hot, open neutral, hot/ground
reversed, hot/neutral reversed. Operation of these analyzers varies by
manufacturer.
- Condition and safety. Check that all wire types and
equipment are installed properly in accordance with good practice. Check the conductors' exposure to
possible damage or abrasion. Look for proper fastening, clearance, and frayed or damaged insulation. Make
certain that all wire splices are made in work boxes and that all boxes for splices and switches have cover
plates. Check all exterior receptacles to make sure they are of the waterproof
type.
- Test: A meg ohm test may be used for detecting
deteriorated insulation. It requires a Megger tester and operates at high voltage. With the electrical
service disconnected, branch circuits should read at least one meg ohm to ground. If lights or appliances
are connected to the circuit, readings should be at least 500,000 ohms. This test should be performed by an
electrician.
- A visual inspection of insulation on accessible
circuits will usually determine whether additional tests should be performed by an electrician. Look for
unprotected wire runs through ducts and other inappropriate areas. Inspect for evidence of" handyman
tampering" (e.g., unconventional splices), and if found in one location, expect it to be more widespread.
Check for surface-mounted lamp cord extension wiring. It is dangerous and must be removed. It is best to
remove all unused wiring or wiring that will be abandoned during rehabilitation work to avoid future
confusion or misuse.
- Aluminum wire. Aluminum wire was used in residential
buildings primarily during the 1960s and early 1970s. Inspect with local code requirements in mind. Be sure
that aluminum wire is attached only to approved devices (marked "CO-ALR" or "ICU-AL") or to approved
connectors. Problems with aluminum wiring occur at connections, so feel all cover plates for heat, smell
for a distinctive odor in the vicinity of outlets and switches, and look for sparks and arcing in switches
or outlets and for flickering lights. Also check for the presence of an oxide inhibitor on all aluminum
wire connections. All such conditions should be corrected. Aluminum wire should not be used on 15 and 20
amp circuits. Whenever possible, aluminum wire and its devices should be replaced with copper wire and
devices appropriate for copper. If aluminum wiring is not replaced, it must be frequently inspected and
maintained.
- Smoke Detectors. Check to see if buildings have
functioning smoke detectors. Detectors should be wired to a power source, and also should contain a
battery. Most likely, buildings built before 1970 will not have detectors, but they should be
added.