Evaluating Your Home's Wiring System
Is knob and tube wiring adequate for modern living? Is your home's electrical
service panel adequate? Here's a guide to inspecting older wiring.
Editor's note: This story is adapted from the
U.S. Department of Housing and Urban Development's Residential Rehabilitation Inspection Guide,
2000.

Found fairly often in houses built before 1930, "knob
and tube" wiring should be carefully inspected to failed insulation and other safety issues. If has
adequate capacity and is otherwise safe, it is still legal in many places.
Electrical systems for small residential buildings are usually simple in concept and
layout. Primary components are the:
- service entry,
- panel board, and
- branch circuits.
In unaltered buildings built since about 1940, the electrical system is likely to
be intact and safe, although it may not provide the capacity required for the planned reuse of the
building. Electrical capacity can be easily increased by bringing additional capacity in from the
street and adding a larger panel board between the service entry and the existing panel. Existing
circuits can continue to use the existing panel and new circuits can be fed through the new panel.
The electrical systems of small residential buildings built prior to about1940 may
require overhaul or replacement, depending on rehabilitation plans and the condition of the electrical
system. Parts of these older systems may function very adequately and they can often be retained if the
rehabilitation isn't extensive and the load-carrying capacity is adequate.
A thorough and informed assessment of the electrical system will determine the
extent to which it can be reused. This assessment should be conducted only by a qualified electrician
who is experienced in residential electrical work. When universal design is a part of a
rehabilitation, consult the Housing and Urban Development publication Residential Remodeling and
Universal Design for detailed information about electrical devices.
| Assessing the
electrical capacity (ampacity) of the building's existing electrical
service |
To determine the capacity (measured in amperes) of the building's existing
electrical service at the main panel-board, check the following:
- The ampacity of the service entry conductor, which may be determined by noting the markings
(if any) on the conductor cable and finding its rated ampacity in the National Electrical
Code, Table 310-16, or applicable local code. If the service entry conductor is in
conduit, look for markings on the conductor wires as they emerge from the conduit into the
panel board. If all conductors are unmarked, have an electrician evaluate them.
- The ampere rating on the panel board or service disconnect switch, as listed on the
manufacturer's data plate.
- The ampere rating marked on the main circuit breaker or main building fuse(s). This rating
should never be higher than the above two ratings; if it is, the system should not be used
until it is evaluated by an electrician.
The building's service capacity is the lowest of the above three figures.
Once the service ampacity has been determined, compare it to the estimated ampacity the building
will require after rehabilitation. If the estimated ampacity exceeds the existing ampacity, the
building's electrical service will need upgrading. The method for estimating required ampacity is found
in the National Electrical Code, Article 220.
Similarly, the service capacity of each branch circuit can be determined by checking the markings on
each branch circuit conductor. If no markings can be found, a plastic wire gauge may be used to measure
the wire size (with the power disconnected), although an experienced person can often determine the
size by eye. Find the ampere rating of the conductor, either by its markings or wire size, in the
National Electrical Code, Table 310-16, or applicable local code.
The safety standards for the following assessment procedures are generally based on the requirements
of the National Electrical Code.

Typical service equipment
Inspect for the following conditions in the electrical service between the street and
the main panel board:
- Overhead wires. Check that overhead wires from the street are no lower than 10 feet above the
ground, not in contact with tree branches or other obstacles, and not reachable from nearby windows
or other accessible areas. Make sure that the wires are securely attached to the building with
insulated anchors, and have drip loops where they enter the weather head. Spliced connections at
the service entrance should be well wrapped, and bare wires from the street should be replaced by
the utility company. Wires should not be located over swimming pools.
- Electric meter. Check that the electric meter and its base are weatherproof, and that the meter
is functional, has not been tampered with, and is securely fastened. Advise the utility company of
any problems with the meter.
- Seismic vulnerability. If the building is in a seismic zone, check the electrical service for
vulnerability to differential movement between the exterior and interior. Look for flexible
connections.
- Service entrance conductor. Ensure that the service entrance conductor has no splices and that
its insulation is completely intact. If the main panel board is located inside the building, the
conductor's passage through the wall should be sealed against moisture. Where aluminum conductors
are used, their terminations at all service equipment should be cleaned with an oxide inhibitor and
tightened by an electrician or replaced with equal capacity copper conductors. When it is necessary
to replace an overhead service entry, have it replaced with an underground service entry.
- Type of power available. Not every jurisdiction provides the same kind of electrical power.
Philadelphia, for example, has two-phase electrical power in some locations rather than the more
common single-phase. Check with the power company to determine the characteristics of the power
available.
The main panel board is the distribution center for electric service within the building and
protects the house wiring from overloads. Inspect the panel board as follows:
- Condition and location. Check the overall condition of the panel board. Water marks or rust on
a panel mounted inside the building may indicate water infiltration along the path of the service
entrance conductor. Panel boards mounted outdoors should be watertight and tamper proof. Panels
mounted indoors should be located as closely as possible to where the service entrance conductor
enters the building and should be easily accessible. The panel board should have a workable and
secure cover.
- Amperage rating. The amperage rating of the main disconnect should not be higher than the
amperage capacity of the service entrance conductor or the panel board. If the rating is higher
(indicating unapproved work has been done), more branch circuits may be connected to it than the
service entrance conductor is capable of supplying. This is a serious hazard and should be
corrected.
- Voltage rating. The voltage rating of the panel board (as marked on the manufacturer's data
plate) should match the voltage of the incoming electrical service.
- Test: The actual voltage rating of the incoming electrical service can be checked with a
voltmeter. This test should be performed by an electrician. Usually three service conductors
indicates 120/240 volt current, and two conductors indicates 120 volt current.
- Grounding. (See illustration below) Verify that the panel board is properly grounded. Its
grounding conductor should run to an exterior grounding electrode or be clamped to the metal water
service inlet pipe between the exterior wall and the water meter. If it is attached on the house
side of the meter, the meter should be jumpered to ensure proper electrical continuity to the
earth. Make sure that the ground conductor is securely and properly clamped to the pipe-often it is
not, and occasionally it is disconnected altogether. Ensure also that the grounding conductor is
not attached to a natural gas pipe, to an inactive pipe that may be cut off on the exterior side of
the wall, or to a pipe that is connected to a plastic water service entry line. If the grounding
conductor is attached to an exterior grounding electrode driven into the earth, verify that the
electrode is installed in accordance with local code. Many older buildings will have the ground
connected to the cold water pipe. If this is the case and the building needs to conform to the
current code, an alternate ground is required. Typical electrical service entry and main panel
board for a single family residence. This type of grounding applies only if the water pipe is
metal. If the water pipe is plastic, a separate driven ground rod is required.

Typical electrical service entry and
main panel board for a single family residence. This type of grounding applies only if the water pipe
is metal. If the water pipe is plastic, a separate driven ground rod is required.
- Test. An electrical ground (resistance-to-ground) test may be used to determine whether the
electrical system is well grounded to the earth. The test requires the use of an ohm-meter and
should be performed by an electrician.
- Over-current protection. Check the rating of the fuse or circuit breaker for each branch
circuit. The amperage of the fuse or circuit breaker should not exceed the capacity of the wiring
in the branch circuit it protects. Most household circuits use #14 copper wire, which should have
15 amp protection. There may be one or more circuits with #12 copper wire, which should have 20 amp
protection. Large appliances, such as electric water heaters and central air conditioners, may
require 30 amp service, which is normally supplied by #10 copper wire. If there is an electric
range, it would require a 40 or 50 amp service with #6 copper wire. Central air conditioning
equipment will have an over-current protection requirement on the nameplate. Aluminum wire must be
one size larger than copper wire in each case (e.g., #14 to #12), but it should not be used for 15
and 20 amp circuits. Make sure that no circuit has a fuse or circuit breaker with a higher ampere
rating than its wiring is designed to carry. Air conditioners and other equipment with motors may
have circuit breakers up to 175 percent ampacity of the conductor rating to allow for starting
current. Look near the panel board for an inordinate number of new or blown fuses, or breakers
taped in the "on" position. Be suspicious of 20 or 25 amp fuses on household lighting circuits.
These are signs of frequent overloads and inadequate electrical service. Other indications of
overloading are the odor of burned insulation, evidence of melted insulation, discolored copper
contact points in the fuse holders, and warm fuses or circuit breakers.
- Test: Flip all circuit breakers on and off manually to make sure they are in good operating
condition. A commercially available circuit breaker and resistance tester, which can simulate an
overload condition, can be used to test each breaker. Such a test should be performed by an
electrician. Note that this test is not recommended for computers, VCR's, clocks, and many similar
devices.
- Many older residential buildings have more than one panel-board or fused devices. Check that
all supplementary over-current devices are located in metal boxes and that they are not in the
vicinity of easily ignitable materials. All panel boards must have covers. It should be possible to
turn off all electrical power to a dwelling from a single location.
The oldest types of residential wiring systems are seldom encountered today. They include open wires
on metal cleats, wiring laid directly in plaster, and wiring in wooden molding. These systems proved
quite hazardous.
The oldest wiring system that may still be acceptable, and one still found fairly often in houses
built before 1930, is "knob and tube." This system utilizes porcelain insulators (knobs) for running
wires through unobstructed spaces, and porcelain tubes for running wires through building components
such as studs and joists.
Note whether knob and tube wiring splices are mechanically twisted, soldered, and taped, as
required. Knob and tube wiring should be replaced during rehabilitation; but if it is properly
installed, needs no modification, has adequate capacity, is properly grounded, has no failed
insulation, and is otherwise in good condition, it can be an acceptable wiring system and is still
legal in some localities.

Check with local building code officials. Also check the terms and conditions of the home insurance
policy in force to see if knob and tube wiring is excluded. In San Diego, knob and tube wiring does not
meet code requirements. It is very difficult to purchase homeowners insurance for properties
containing knob and tube wiring. The greatest problem with such wiring is its insulation,
which turns dry and brittle with age and often falls off on contact, leaving the wire exposed.
Insulation that can be seen to have failed also will likely have failed where wiring is concealed. If
any failed insulation is observed, the knob and tube wiring should be replaced.
Other approved wire types include:
- NM (non-metallic) cable, often called by the trade name "Romex," a plastic covered-cable for
use in dry locations (older NM cable may be cloth covered).
- NMC, similar to NM but rated for damp locations.
- UF (underground feeder), a plastic-covered waterproof cable for use underground.
- AC (armored cable), also called BX, a flexible metal-covered cable.
- MC (metal-clad cable), a flexible metal-covered cable with a green insulated ground
conductor.
- EMT (electrical metallic tubing), also called "thin wall," a metal conduit through which the
wires are run in areas where maximum protection is required.
In the picture at right,
the armored cable and junction box are in good shape and can be reused, even if the lighting
fixture is relocated.
Check branch circuits for the following:
- Marking. The function of each branch circuit should be clearly and legibly marked at its
disconnect, fuse, circuit breaker, or on the directory on the panel board.
- Connected loads. Trace branch circuit conductors to determine that their connected load does
not exceed their rating (e.g., a 30 amp clothes dryer connected to a 20 amp circuit). Generally
speaking, each dwelling unit should have two to four 15 amp circuits for lighting and convenience
outlets; two 20 amp circuits for appliances in the kitchen, dining, and laundry areas; and separate
circuits of appropriate ampacity for large appliances such as dryers, ranges, disposals,
dishwashers, and water heaters.
- Check the size and length of all branch circuit wiring against the requirements of the local
electrical code. Buildings built before 1980 may be considered to have an inadequate number of
circuits because present day codes require a separate laundry circuit and a separate circuit for
the bathroom receptacle. For air conditioning units, many local codes will allow one wire size
smaller than called for in the disconnect.
- Test: A voltmeter may be used to measure voltage drop due to excessive branch circuit length,
poor wiring connections, or undersized wire. Measurements must be made under a connected load. This
test should be performed by an electrician.
- Grounding. It is best that all circuits be grounded to the panel board, but this was not
required by the National Electrical Code prior to 1965. Do not assume that circuits in metal cable
are grounded without testing each outlet. Also, do not assume that three-prong plug convenience
outlets are connected to ground. Remove each one to observe the presence of a connected ground
wire. Check to see whether GFI (ground fault interruption) type receptacles have been installed in
laundries, kitchens, and bathrooms, and test their operation. These types of receptacles were not
required before 1990, but are easily installed as replacements.
- Test: Commercially available circuit analyzers can be used for checking the following circuit
conditions: open ground, open hot, open neutral, hot/ground reversed, hot/neutral reversed.
Operation of these analyzers varies by manufacturer.
- Condition and safety. Check that all wire types and equipment are installed properly in
accordance with good practice. Check the conductors' exposure to possible damage or abrasion. Look
for proper fastening, clearance, and frayed or damaged insulation. Make certain that all wire
splices are made in work boxes and that all boxes for splices and switches have cover plates. Check
all exterior receptacles to make sure they are of the waterproof type.
- Test: A meg ohm test may be used for detecting deteriorated insulation. It requires a Megger
tester and operates at high voltage. With the electrical service disconnected, branch circuits
should read at least one meg ohm to ground. If lights or appliances are connected to the circuit,
readings should be at least 500,000 ohms. This test should be performed by an electrician.
- A visual inspection of insulation on accessible circuits will usually determine whether
additional tests should be performed by an electrician. Look for unprotected wire runs through
ducts and other inappropriate areas. Inspect for evidence of" handyman tampering" (e.g.,
unconventional splices), and if found in one location, expect it to be more widespread. Check for
surface-mounted lamp cord extension wiring. It is dangerous and must be removed. It is best to
remove all unused wiring or wiring that will be abandoned during rehabilitation work to avoid
future confusion or misuse.
- Aluminum wire. Aluminum wire was used in residential buildings primarily during the 1960s and
early 1970s. Inspect with local code requirements in mind. Be sure that aluminum wire is attached
only to approved devices (marked "CO-ALR" or "ICU-AL") or to approved connectors. Problems with
aluminum wiring occur at connections, so feel all cover plates for heat, smell for a distinctive
odor in the vicinity of outlets and switches, and look for sparks and arcing in switches or outlets
and for flickering lights. Also check for the presence of an oxide inhibitor on all aluminum wire
connections. All such conditions should be corrected. Aluminum wire should not be used on 15 and 20
amp circuits. Whenever possible, aluminum wire and its devices should be replaced with copper wire
and devices appropriate for copper. If aluminum wiring is not replaced, it must be frequently
inspected and maintained.
- Smoke Detectors. Check to see if buildings have functioning smoke detectors. Detectors should
be wired to a power source, and also should contain a battery. Most likely, buildings built before
1970 will not have detectors, but they should be added.
|